depiction:


AW22b_

Wall: exposed to outside air – not back-ventilated (BG1) – IBO benchmarks 2020
login and edit copy of this building element
0,119 W/m²K
A++
A+
A
B
C
D
E
F
G
OI-Class (BG1)²
D
mass 103,9 kg/m²
PENRT 1191 MJ/m²
GWP total -4,54 kg CO2/m²
AP 0,530 kg SO2/m²
no. type layer (from inside to outside) d
cm
λ
W/mK
R
m²K/W
ΔOI3
pts/m²
1 homogene Schichthomogene Schicht Rigips Feuerschutzplatte (Rigips Feuerschutzplatte) 1,25 0,250 0,05 2
2 homogene Schichthomogene Schicht Rigips Feuerschutzplatte (Rigips Feuerschutzplatte) 1,25 0,250 0,05 2
3 inhomogene Schicht mit 2 Subschichteninhomogene Schicht mit 2 Subschichten inhomogeneous (parts vertical) 7,00      
    56,5 cm (65%) ISOVER KONTUR KP 1- 035 5,00 0,034 1,47 4
    56,5 cm (26%) Vertical air layer, heat flow up 16 < d <= 20 mm 2,00 0,133 0,15 0
    6 cm (10%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 7,00 0,120 0,58 0
4 homogene Schichthomogene Schicht Brettsperrholz BBS (5-lagig) (binderholz Brettsperrholz BBS (Fichte)) 10,00 0,120 0,83 16
5 homogene Schichthomogene Schicht Mineralwolle Isover Sillatherm WVP 1-035 (ISOVER Sillatherm WVP 1-035) 20,00 0,034 5,88 85
6 homogene Schichthomogene Schicht Putzfassade (Synthesa Pergit Reibputz Plus) 0,70 0,910 0,01 1
    Rsi / Rse = 0,130 / 0,040  
    R' / R'' (max. relative error: 1,0%) = 8,503 / 8,328  
    building element 40,20   8,416 110

¹ U value (Heat transfer coefficient) calculated according to ÖNORM EN ISO 6946.
² For the OI class, the U-value of the component is taken into account in addition to the ecological key figures