Abbildung: Aussenwand - Leichtbau (Zellulose + Holzfaser)

Wall: exposed to outside air – back-ventilated (BG1) – IBO benchmarks 2012 project: Beispiel client: EIV
login and edit copy of this building element
A++
RL6
0,148 W/m²K
A++
A+
A
B
C
D
E
F
G
OI-Class (BG1)4
A++
mass 81,1 kg/m²
PENRT 538 MJ/m²
GWP total -72,6 kg CO2/m²
AP 0,148 kg SO2/m²
no. type layer (from inside to outside) d
cm
λ
W/mK
R
m²K/W
ΔOI3
pts/m²
1 homogene Schichthomogene Schicht Gypsum plasterboard (700 kg/m³) 1,25 0,210 0,06 3
2 homogene Schichthomogene Schicht Gypsum plasterboard (700 kg/m³) 1,25 0,210 0,06 3
3 inhomogene Schichtinhomogene Schicht inhomogeneous (parts vertical) 5,00      
    106 cm (96%) Wood fibre WF-W (50 kg/m³) 5,00 0,042 1,19 2
    4 cm (4%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 5,00 0,120 0,42 0
4 homogene Schichthomogene Schicht Polyethylene (PE) vapour brake 0,10 0,500 0,00 ¹ 3
5 homogene Schichthomogene Schicht OSB boards (650 kg/m³) 1,80 0,130 0,14 4
6 inhomogene Schichtinhomogene Schicht inhomogeneous (parts vertical) 24,00      
    80 cm (89%) Cellulose vertical cavity wall insulation (54 kg/m³) 24,00 0,041 5,85 6
    10 cm (11%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 24,00 0,120 2,00 -1
7 homogene Schichthomogene Schicht OSB boards (650 kg/m³) 1,80 0,130 0,14 4
8 homogene Schichthomogene Schicht Building paper 0,01 0,170 0,00 ¹ 0
9 inhomogene Schichtinhomogene Schicht inhomogeneous (parts vertical) 5,00      
    86 cm (96%) Vertical air layer, horizontal heat flow 45 < d <= 50 mm 5,00 ² ² ¹ 0
    4 cm (4%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 5,00 ² ² ¹ 0
10 inhomogene Schichtinhomogene Schicht inhomogeneous (parts horizontal) 2,50      
    0,8 cm (17%) Vertical air layer, horizontal heat flow 20 < d <= 25 mm 2,50 ² ² ¹ 0
    4 cm (83%) Timber (525 kg/m³ - e.g. larch) - planed, technically dried 2,50 ² ² ¹ 1
    Rsi / Rse = 0,130 / 0,130  
    R' / R'' (max. relative error: 2,2%) = 6,897 / 6,595  
    building element 42,71   6,746 26

¹ layer is OI-relevant from BG1
² not relevant
³ U value (Heat transfer coefficient) calculated according to ÖNORM EN ISO 6946. A++: U-Werte im Bereich der Markierung A++ (0,13 W/m²K) sind notwendig, um derartige Gebäude zu errichten. RL6: OIB Richtlinie 6 (April 2007); In ganz Österreich seit 1.1.08 verbindlich festgelegter max. U-Wert (0,35 W/m²K) für alle Neubauten sowie instandgesetzte bzw. erneuerte Bauteile.
4 For the OI class, the U-value of the component is taken into account in addition to the ecological key figures