depiction:


AW 05: Ziegelmauerwerk

Wall: exposed to outside air – not back-ventilated (BG1) – IBO benchmarks 2012 project: Althaussanierung - Bestand (Beispiel) client: EIV
login and edit copy of this building element
A++
RL6
1,349 W/m²K
A++
A+
A
B
C
D
E
F
G
OI-Class (BG1)²
G
mass 312,0 kg/m²
PENRT 649 MJ/m²
GWP total 54,8 kg CO2/m²
AP 0,149 kg SO2/m²
no. type layer (from inside to outside) d
cm
λ
W/mK
R
m²K/W
ΔOI3
pts/m²
1 homogene Schichthomogene Schicht Normal plastering mortar GP lime cement (1800 kg/m³) 2,00 1,050 0,02 4
2 homogene Schichthomogene Schicht Vertically perforated brick (old pre-1980 stock) + normal mortar for brickwork (1000 kg/m³) 24,00 0,450 0,53 42
3 homogene Schichthomogene Schicht One-layer plastering mortar for external OC lime cement mortar (1800 kg/m³) 2,00 1,050 0,02 4
    Rsi / Rse = 0,130 / 0,040  
    R' / R'' (max. relative error: 0,0%) = 0,741 / 0,741  
    building element 28,00   0,741 51

¹ U value (Heat transfer coefficient) calculated according to ÖNORM EN ISO 6946. A++: U-Werte im Bereich der Markierung A++ (0,13 W/m²K) sind notwendig, um derartige Gebäude zu errichten. RL6: OIB Richtlinie 6 (April 2007); In ganz Österreich seit 1.1.08 verbindlich festgelegter max. U-Wert (0,35 W/m²K) für alle Neubauten sowie instandgesetzte bzw. erneuerte Bauteile.
² For the OI class, the U-value of the component is taken into account in addition to the ecological key figures