AW 08a: Holzblockwand saniert (Flachs)

Wall: exposed to outside air – back-ventilated (BG1) – IBO benchmarks 2012 project: Althaussanierung - Messemodell client: EIV
login and edit copy of this building element
A++
RL6
0,151 W/m²K
A++
A+
A
B
C
D
E
F
G
OI-Class (BG1)4
A++
mass 143,1 kg/m²
PENRT 630 MJ/m²
GWP total -202 kg CO2/m²
AP 0,186 kg SO2/m²
no. type layer (from inside to outside) d
cm
λ
W/mK
R
m²K/W
ΔOI3
pts/m²
1 homogene Schichthomogene Schicht Holztäfer (Timber (525 kg/m³ - e.g. larch) - rough, technically dried) 2,00 0,130 0,15 0
2 inhomogene Schichtinhomogene Schicht inhomogeneous (parts horizontal) 3,00      
    56,5 cm (90%) Vertical air layer, horizontal heat flow 25 < d <= 30 mm 3,00 0,176 0,17 0
    6 cm (10%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 3,00 0,120 0,25 0
3 homogene Schichthomogene Schicht Holzblockwand (Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried) 20,00 0,120 1,67 -4
4 homogene Schichthomogene Schicht Building paper 0,10 0,170 0,01 ¹ 1
5 inhomogene Schichtinhomogene Schicht inhomogeneous (parts vertical) 10,00      
    56,5 cm (90%) Hemp fibre insulation (41 kg/m³) 10,00 0,045 2,22 6
    6 cm (10%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 10,00 0,120 0,83 0
6 inhomogene Schichtinhomogene Schicht inhomogeneous (parts horizontal) 10,00      
    56,5 cm (90%) Hemp fibre insulation (41 kg/m³) 10,00 0,045 2,22 6
    6 cm (10%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 10,00 0,120 0,83 0
7 homogene Schichthomogene Schicht Wood fibre WF-W (180 kg/m³) 2,00 0,051 0,39 3
8 homogene Schichthomogene Schicht Building paper 0,10 0,170 0,01 ¹ 1
9 inhomogene Schichtinhomogene Schicht inhomogeneous (parts vertical) 5,00      
    57,5 cm (92%) Vertical air layer, heat flow up 46 < d <= 50 mm 5,00 ² ² ¹ 0
    5 cm (8%) Timber (475 kg/m³ - e.g. spruce/fir) - rough, technically dried 5,00 ² ² ¹ 0
10 homogene Schichthomogene Schicht Holzschirm (Timber (525 kg/m³ - e.g. larch) - planed, technically dried) 2,50 ² ² ¹ 1
    Rsi / Rse = 0,130 / 0,130  
    R' / R'' (max. relative error: 2,2%) = 6,785 / 6,492  
    building element 54,70   6,638 12

¹ layer is OI-relevant from BG1
² not relevant
³ U value (Heat transfer coefficient) calculated according to ÖNORM EN ISO 6946. A++: U-Werte im Bereich der Markierung A++ (0,13 W/m²K) sind notwendig, um derartige Gebäude zu errichten. RL6: OIB Richtlinie 6 (April 2007); In ganz Österreich seit 1.1.08 verbindlich festgelegter max. U-Wert (0,35 W/m²K) für alle Neubauten sowie instandgesetzte bzw. erneuerte Bauteile.
4 For the OI class, the U-value of the component is taken into account in addition to the ecological key figures